One of the tests carried out on a transformer after assembly is the lightning impulse test, for assessment of the integrity of its winding insulation. In the case of a fault, it has been well established that the pattern of the fault currents contains a typical signature of the nature and location of the insulation failure involved. This paper describes a new approach using the 'wavelet transforms' to classify the patterns inherent in different fault currents. Whereas conventional frequency-response analysis based techniques fail to identify the time-localization of a particular frequency component in a time-dependent signal, the wavelets are not only localized in frequency, but also in time. The 'time-frequency localization' feature of wavelet transform is employed for pattern classification of impulse fault currents of transformers. Results for simulated models of 3, 5 and 7 MVA transformers are presented to illustrate the ability of this approach to classify insulation failures.
No takes yet. Share an insight, caveat, or question.
Purkait et al. (2002) studied this question.