Answers are grounded in this paper and cite their sources.
The cascaded H-bridge (CHB) low-capacitance static compensator (LC-StatCom) has a limited negative-sequence current injection capability compared to a conventional CHB StatCom, due to the comparatively larger oscillations on the capacitor voltages. Placing limits on the ability to provide negative-sequence current to the grid for a given capacitor size is required to prevent overmodulation. This article shows that these limits can be maximized by injecting an optimal third-harmonic circulating current. The effects of injecting the third-harmonic current on the capacitor voltages, both in balanced and unbalanced grid voltage conditions, are analyzed. Specifically, the procedure allows the knowledge of the potential capability of the LC-StatCom when injecting negative-sequence currents. The procedure is based on a linear programming approach. Although the procedure is applicable to any CHB StatCom, regardless of the submodule capacitor size, it is particularly important in LC-StatComs. To corroborate the proposed analysis, simulation and experimental results under balanced and unbalanced grid voltage conditions are presented.
No takes yet. Share an insight, caveat, or question.
Rodríguez et al. (2022) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: