Answers are grounded in this paper and cite their sources.
Generalized short-circuit ratio (gSCR) for gird strength assessment of multi-infeed high voltage direct current (MIDC) systems is a rigorous theoretical extension of the traditional SCR, which enables SCR to be extended to MIDC systems. However, gSCR was originally based on the assumption of homogeneous MIDC systems, in which all HVDC converters have an identical control configuration, thus presenting challenges to applications of gSCR to inhomogeneous MIDC systems. To weaken this assumption, this study applies matrix perturbation theory to explore the possibility of utilization of gSCR into inhomogeneous MIDC systems. Results of numerical experiments show that in inhomogeneous MIDC systems, the previously proposed gSCR can still be used without modification. However, critical gSCR (CgSCR) must be redefined by considering the characteristics of HVDC converter control configurations. Accordingly, the difference between gSCR and redefined CgSCR can effectively quantify the pertinent ac grid strength in terms of the static voltage stability margin. The performance of our proposed method is demonstrated in a tripleinfeed inhomogeneous line commutated converter based high voltage direct current (LCC-HVDC) system.
No takes yet. Share an insight, caveat, or question.
Wang et al. (2023) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: