Answers are grounded in this paper and cite their sources.
In this research work, the design and implementation of a 154-kV±50-Mvar transmission static synchronous compensator (T-STATCOM) have been carried out primarily for the purposes of reactive power compensation and terminal voltage regulation and secondarily for power system stability. The implemented T-STATCOM consists of five 10.5-kV±12-Mvar cascaded multilevel converter (CMC) modules operating in parallel. The power stage of each CMC is composed of five series-connected H-bridges (HBs) in each phase, thus resulting in 21-level line-to-line voltages. Due to modularity and flexibility of implemented HBs, each CMC module has reached a power density of 250kvar/m³, thus making the mobility of the system implementable. DC-link capacitor voltages of HBs are perfectly balanced by means of the modified selective swapping algorithm proposed. The field tests carried out at full load in the 154-kV transformer substation where T-STATCOM is installed have shown that the steady-state and transient responses of the system are quite satisfactory.
No takes yet. Share an insight, caveat, or question.
Gultekin et al. (2012) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: