Answers are grounded in this paper and cite their sources.
SUMMARY Frequency response analysis (FRA) is a powerful technique to detect internal abnormalities within power transformers. However, diagnosis criteria of power transformers by FRA have not been fully established yet. In this paper, a new evaluation method of degree of identification between two transfer functions is proposed. In the proposed method, a frequency window is employed and cross‐correlation factor is calculated with moving the window. Furthermore, the proposed method is applied to transfer functions of real transformers with or without some abnormalities. Based on this discussion, objective criteria for diagnosis of abnormalities of transformer windings by FRA are proposed. The proposed criteria are based on a few data of transformers with some abnormalities. Therefore, the proposed criteria are tentative and they would be improved by accumulation of further data.
No takes yet. Share an insight, caveat, or question.
Miyazaki et al. (2017) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: