This is the authors' abstract. We don't add key points for this paper.
This paper presents a comparative study of neural network (NN) efficiency for the detection of incipient faults in power transformers. The NN was trained according to five diagnosis criteria commonly used for dissolved gas analysis (DGA) in transformer insulating oil. These criteria are Doemenburg, modified Rogers, Rogers, IEC, and CSUS. Once trained, the NN was tested by using a new set of DGA results. Finally, NN diagnosis results were compared with those obtained by inspection and analysis. The study shows that the NN rate of successful diagnosis is dependant on the criterion under consideration, with values in the range of 87-100%.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Guardado et al. (2001) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: