A methodology is proposed and applied to determine the variation of soil resistivity and permittivity in the typical range of lightning current frequency components. The response of horizontal electrodes buried in high- and low-resistivity soils subjected to currents with lightning waveform patterns was measured and also simulated, taking this variation into account. The waves of the simulated and measured grounding potential rise are nearly the same but are quite different from the simulated waves considering the conventional assumption of constant values for soil resistivity and permittivity.