This paper proposes a method of sharing power/energy between multiple sources and multiple loads using an integrated magnetic circuit as a junction between sources and sinks. It also presents a particular use of the magnetic circuit as an ac power supply, delivering sinusoidal voltage to load irrespective of the presence of the grid, taking only active power from the grid. The proposed magnetic circuit is a three-energy-port unit, viz.: 1) power/energy from grid; 2) power energy from battery-inverter unit; and 3) power/energy delivery to the load in its particular application as quality ac power supply (QPS). The product provides sinusoidal regulated output voltage, input power-factor correction, electrical isolation between the sources and loads, low battery voltage, and control simplicity. Unlike conventional series-shunt-compensated uninterruptible power supply topologies with low battery voltage, the isolation is provided using a single magnetic circuit that results in a smaller size and lower cost. The circuit operating principles and analysis, as well as simulation and experimental results, are presented for this QPS.