This paper presents ultra-wide bandwidth measurements of partial discharge (PD) current pulses. Using a 33 GHz bandwidth oscilloscope together with a direct, matched coaxial connection to the PD source, pulses have been characterized with a greater degree of accuracy than has previously been achieved, with a minimum observed rise time of 24 ps. The PD source consists of a sharp protrusion in pressurized sulfur hexaflouride (SF6) with a tip radius of 25 µm. Both positive and negative corona pulses were recorded, revealing previously indistinguishable frequency content and features such as the appearance of groups of multiple component pulses occurring within a nanosecond time scale. The upper bandwidth limitation of the complete measurement set-up was established. This was calculated by cross-correlating current pulses with corresponding pulses filtered at lower frequencies to determine their similarity. The tendency for multiple consecutive pulses to occur within a short time period was evident. The results provide valuable data for researchers investigating fundamental physical phenomena of SF6 ionization and PD activity.