This paper describes a digital technique for protecting power transformers. The technique uses positive- and negative-sequence models of the power system in a fault-detection algorithm. While phase voltages and currents at the transformer terminals are used to detect a fault, no information concerning parameters of the transformer and power system is required. The performance of the proposed technique was studied for a variety of operating conditions using data generated by EMTP simulations. The impact of ratio-mismatch and saturation of current transformers on the performance of the technique was also examined. Results indicate that the proposed technique is stable during these conditions.
No takes yet. Share an insight, caveat, or question.
Sidhu et al. (1999) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: