Physical models which are representative of the materials, construction, and dimensions of power transformer duct structures have been fabricated for both core- and shell-form designs. Electrification characteristics have been documented as a function of the parameters of practical interest, and the results obtained have the general character of those found in earlier studies. However, partial discharges have only been detected under worst-case conditions for the blocking structure associated with the shell-form configurations which generate more charge than the corresponding conditions in the core-form construction.>