This paper describes an integrated control and protection scheme for the power conditioner used by the medium rating grid-connected distributed generators and storage devices. The proposed control scheme consists of two loops: a steady-state loop that achieves optimum harmonic output by selective elimination of low-order harmonics and a transient loop based on space vector methods that enhances the transient response of the generator and provides overcurrent protection and fault rejection. The paper presents simulation studies of a grid-connected storage device equipped with a controller based on the proposed scheme. The results of these studies demonstrate the robustness of the controller to varying line conditions and disturbances.
No takes yet. Share an insight, caveat, or question.
Hatziadoniu et al. (2003) studied this question.
Synapse has enriched 4 closely related papers on similar clinical questions. Consider them for comparative context: