A full-order, voltage-behind-reactance synchronous machine model has recently been proposed in the literature. This paper extends the voltage-behind-reactance formulation for the electromagnetic transient program (EMTP)-type solution, in which the rotor subsystem is expressed in qd coordinates and the stator subsystem is expressed in abc phase coordinates. The model interface with the nodal-analysis network solution is non-iterative and simultaneous. An example of a single-machine, infinite-bus system shows that the proposed model is more accurate and efficient than several existing EMTP machine models
No takes yet. Share an insight, caveat, or question.
Wang et al. (2006) studied this question.