This paper proposes a coordinated voltage regulation scheme for on-load tap changer (OLTC) and renewable distributed generation (DG) units to provide a proper voltage regulation for active distribution systems. The main motivation of applying fuzzy logic is that it can deal with environments of imperfect information, and thus, it can reduce communication requirements. The proposed regulation scheme consists of three fuzzy-based control algorithms. The first control algorithm is proposed for the OLTC such that it can mitigate the effect of DG units on the voltage profile. The second control algorithm is proposed to provide a DG reactive power sharing, in order to relax the OLTC tap operation. The third control algorithm aims to partially curtail DG active powers to restore a feasible solution from the OLTC prospective. The proposed fuzzy algorithms have the advantage of providing proper voltage regulation with relaxed tap operation, utilizing only the estimated system minimum and maximum voltages. Moreover, it avoids numerical instability and convergence problems associated with centralized approaches, as it does not require to run an optimization algorithm. Real-time simulations are developed to show the effectiveness of the proposed fuzzy algorithms on a typical distribution network, using OPAL-RT real-time simulator.