Experimental study demonstrates elevated frictional pressure drop in ammonia return bends at low temperatures, highlighting geometric and thermal influences on refrigeration systems.
The performance of a refrigeration system depends on the refrigerant pressure drop and heat transfer. While single-tube void fraction and pressure drop data are plentiful, research on U-bends is limited, especially for ammonia at low saturation temperatures. Ammonia’s comparatively higher liquid-to-vapor density ratio results in a higher void fraction and thus affects the local pressure drop. This paper presents two-phase flow pressure-drop characteristics of ammonia in return bends and contiguous straight tubes at a saturation temperature of -24 °C. Experiments were conducted on tubes with nominal outer diameters ( d o ) of 9.5 and 15.9 mm, and bend radii-to-diameter ratios ( R/d o ) of 1.2 and 2.5 for both tubes. Three orientations of the return bend were studied, i.e., horizontal, vertical upward, and vertical downward. Mass flux was varied between 30 and 60 kg m⁻² s⁻¹ for the small tube and 15–30 kg m⁻² s⁻¹ for the medium tube at various vapor quality. The pressure drop increased with mass flux and vapor quality, as well as with lower tube diameters. For the return bends, a higher pressure drop occurred at a smaller R/d o ratio; however, bend orientation had a mixed effect on the pressure drop. The return bends primarily showed higher pressure drops than straight tubes under similar experimental conditions. Pressure drop measured in the return bend of a small-diameter tube at low saturation temperatures was 40–80% higher than that of the authors’ previous work at medium saturation temperature due to higher liquid viscosity and vapor specific volume.
No takes yet. Share an insight, caveat, or question.
Cremaschi et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: