The DC characteristics of XLPE (crosslinked polyethylene) power cables were investigated. Cables with an insulation thickness of 2.5 mm, 9 mm, and 13 mm using either XLPE or conductive-inorganic-filled XLPE (XL-A) were manufactured, and four kinds of breakdown tests (DC, polarity reversal, impulse, and superposing opposite polarity impulse on DC prestress) were performed. A 250 kV, XL-A cable (20 mm thickness) was designed and manufactured using the results. The test results show that the XL-A cable possesses much better DC breakdown characteristics than the XLPE cable and is adequate for use in DC cables.>
No takes yet. Share an insight, caveat, or question.
Ogata et al. (1990) studied this question.