In this paper, the authors have developed a hardware model for blocking even and odd harmonics of a power transformer. In the proposed hardware model, intelligent differential & over-current relays are used for the blocking of harmonics of a power transformer. The harmonic restraint function on the differential relay (7UT61) prevents the relay from tripping during transformer magnetizing inrush current. However, the over-current relays which are used for back up protection does not have a harmonic restraint element, and over-current relay trips due to magnetizing inrush current, causes unwanted interruptions and power failures. The establishment of harmonic blocking scheme for over-current protection in power transformers is an important finding of this research study. IEC61850 standard-Based GOOSE (Generic Object Oriented Substation Event) applications used in power transformer protection for fast detecting and clearing of faults is an interested study presented in the proposed work.
No takes yet. Share an insight, caveat, or question.
Azeem et al. (2021) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: