Grid-synchronising Stability (GSS) is an emerging issue that exists in grid-feeding voltage-source converters (VSCs). Its occurrence is primarily related to the nonlinear dynamics of a type of vastly applied synchronization units - Phase-locked Loops (PLL). Dynamic characterisation and modelling for the GSS analysis can be achieved by using a simplified system model, which is a second-order and autonomous nonlinear equation; however, with the presence of an indefinite damping term. As revealed and demonstrated in this work, this indefinite damping effect can result in an inaccurate Region-of-Attraction (ROA) estimation of the traditional Equal Area Principle (EAP)-based method. To overcome this issue and achieve a valid ROA estimation, this paper adopts the sum-of-squares (SOS) programming technique, which is a numeric optimisation method with SOS relaxations. The development and implementation of the SOS program for ROA estimation are presented. Numerical case studies and time-domain verifications demonstrate that this method is valid for GSS analysis, and an almost precise estimation is achieved in the first quadrant. This evidence makes the SOS method a promising tool for GSS analysis because the GSS problem is most concerned with the stability within the first swing cycle, i.e., in the first quadrant.