The effect of dc poling time upon the time-dependent decay of space charge in insulation peelings of cross-linked polyethylene (XLPE) cable that had not previously experienced either electrical or thermal stressing is investigated. Two dc poling durations were used, 2 h and 26 h at an electric field of 50 kV mm−1 and at ambient temperature. Space charge was measured in the two samples investigated both during space charge accumulation and throughout its subsequent decay. The results show that the length of dc poling plays an important role in the subsequent decay. Despite the fact that both samples have had the same amount of space charge by the end of both short and long poling durations the time dependence of the space charge decay is different. Most of the charge stored in the sample that had experienced the short time poling decays rapidly after voltage removal. On the other hand, the charge that is stored in the sample with the long dc poling duration decays slowly and its decay occurs in two stages. The data, which are analysed by means of the de-trapping theory of space charge decay, imply that the charge stored in the material has occupied energy states with different trap depth ranges. The two poling durations lead to different relative amounts of charge in each of the two trap depth ranges. Possible reasons for this are discussed.