Answers are grounded in this paper and cite their sources.
In this paper, we present a Fingerprint Linear Estimation Routine to identify topology changes in power networks using readings from sparsely deployed phasor measurement units (PMUs). When a power line, load, or generator trips in a network, or when a substation is reconfigured, the event leaves a unique “voltage fingerprint” of bus voltage changes that we can identify using only the portion of the network directly observed by the PMUs. The naive brute-force approach to identify a failed line from such voltage fingerprints, though simple and accurate, is slow. We derive an approximate algorithm based on a local linearization and a novel filtering approach that is faster and only slightly less accurate. We present experimental results by using the IEEE 57-bus, IEEE 118-bus, and Polish 1999-2000 winter peak networks.
No takes yet. Share an insight, caveat, or question.
Ponce et al. (2017) studied this question.