Answers are grounded in this paper and cite their sources.
Current Transformers (CTs) saturation leads to distortion of current waveform and operational malfunction of protection relays. This paper introduces a practical and simple method to prevent CTs saturation. The method uses a negative voltage feedback and applies it to CT secondary side. The injected voltage opposes the excitation voltage of CT in a manner that the magnetic flux of CT remains almost constant under saturation level for any faults. The method is categorized as a hardware solution, does not need to detect the CT saturation time and works either for digital or non-digital relays. The method is verified in a wide range of simulations and experimental results. The obtained results show that the method is reliable, effective, and accurate.
No takes yet. Share an insight, caveat, or question.
Delzendeh et al. (2019) studied this question.