To make better use of local generators' dynamic var reserve to improve short-term voltage stability (STVS), this paper proposes an integrated high side var-voltage control (IHSV2C) for power plants in receiving-end power systems. The IHSV2C consists of a plant-level multi-machine var coordinator (MMVC) and several unit-level high side voltage controllers (HSVCs). MMVC coordinates the reactive power output among generators and provides control parameters for HSVCs, while HSVCs can maintain the voltage of a pre-defined voltage control point (VCP) by regulating the voltage reference of the excitation control of each generator. Therefore, when the system suffers a serious fault, IHSV2C can drive the generators to provide stronger var support. Consequently, the voltage stability can be improved. A conceptual model of the receiving-end power system in China Southern Power Grid (CSG) is established, and the IHSV2C has been validated through a simulation analysis on the system. Both time-domain simulation results and the voltage sag severity index (VSSI) have fully demonstrated its performance. Therefore IHSV2C offers a new and effective approach to improve STVS of receiving-end power systems.