Answers are grounded in this paper and cite their sources.
The equations and parameters of a physical arc model which can be used to compare test circuits with respect to the thermal and dielectric interrupting interval of SF/sub 6/ circuit breakers are presented. An example calculation with the alternative transient program (ATP) shows the interruption of a terminal fault with a four-parameter TRV. The sensitivity of the arc model in the thermal interrupting interval is demonstrated by comparing artificial line circuits.>
No takes yet. Share an insight, caveat, or question.
Sluis et al. (1992) studied this question.