In this study a new model for calculating shielding requirements in diagnostic X-ray facilities is presented. It is based on the combination and modification of models and concepts originally proposed by other authors in order to calculate barrier requirements in diagnostic X-ray facilities accurately and realistically without unjustified exaggerations. With this model, multiple sources of radiation operating at different potentials, leakage radiation reduction when operating at potentials less than the maximum rated value, secondary radiation use factors reduction for primary barriers, attenuation by image receptor hardware and existing building materials are all taken into account. Examples of shielding calculations for typical cases are given illustrating the differences between the various models and concepts proposed, as well as the potential reduction in shielding requirements without compromising the radiation protection of public and staff.
No takes yet. Share an insight, caveat, or question.
Tsalafoutas et al. (2003) studied this question.
Synapse has enriched 2 closely related papers on similar clinical questions. Consider them for comparative context: