A reliability model is described which more closely simulates the states of power systems during faults than do the usual "two-state" models. This is achieved primarily by modelling the effects of comnponent failures on the system through three-state cycles, which include a state following the fault and another after the failed device is isolated, through switching, for repair. The effects of component maintenance are also incorporated. A sample study is presented, wherein the average outage frequency and duration of a small 115-kV network are calculated. The findings include the observations that, in most cases, the effects of all but the lowest contingency system failures can be neglected; and that coincidences of failures and maintenance are often more frequent causes of system outages than coincidences of faults.
No takes yet. Share an insight, caveat, or question.
J. Endrenyi (1971) studied this question.
Synapse has enriched 4 closely related papers on similar clinical questions. Consider them for comparative context: