CF3I and mixed gases containing CF3I are potential substitutes of SF6in electrical equipment. In this paper, we studied the feasibility of replacing SF6with CF3I/N2in terms of power frequency breakdown performance under the influence of gas pressure, mixing ratio, and electric field. The synergistic effect, liquefaction temperature, and self-recover ability of CF3I/N2were analyzed. Experimental results showed that, under a highly uniform electric field, the sensitivity of the power frequency breakdown characteristics of the gases to pressure shows the order SF6CF3IN2. The power frequency AC breakdown strength of CF3I/N2(30%/70%) at electrode distances of 5 and 10 mm could reach over 0.9 and 0.85 times that of SF6at 0.3 MPa, respectively. CF3I/N2showed positive synergistic effects and the improvement was attributed to N2. CF3I presents excellent self-recoverability. The optimum ratio of CF3I/N2to replace SF6gas as insulating medium is 30% at 0.3 MPa.
No takes yet. Share an insight, caveat, or question.
Xiao et al. (2016) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: