China’s East–Data–West–Computing strategy places data centers in cooler climates, but climate alone does not determine water savings. This study combines public cooling evidence, hourly weather data for 2015–2024, a physical heat-rejection model, and provincial electricity-water factors in a project-specific break-even analysis. An audit of 93 mapped records identifies 12 unique western hub projects and four named or cluster-level eastern alternatives, yielding 48 comparisons. Cooling operation is reconstructed from public evidence where possible and otherwise represented by explicit climate-based scenarios. Under the central assumptions, western combined operational water intensity is lower in 27 of 48 pairs, with changes ranging from −63.5% to +110.4%. Against Guangdong, matched wet-tower designs and facility energy efficiency yield higher mean western consumption because of electricity-related water use. Low-water configurations can reverse this penalty, but their advantage depends on the eastern alternative, facility energy overhead, and electricity supply. Local water stress adds a separate constraint on residual campus demand. Westward siting therefore saves operational water only when the destination project crosses the threshold set by the eastern alternative it replaces.