This study investigates the impact of phase‐locked loop (PLL) and DC‐side voltage controller on small‐signal dynamics of the high‐voltage direct‐current (HVDC) inverter station system which utilises line commutated converter (LCC) technology. The studies are conducted based on eigenanalysis of a linearised model of a study system and verified by time‐domain simulation studies in the PSCAD platform. The studies show that under weak grid conditions, e.g. short‐circuit ratio (SCR) = 1, parameters of PLL and DC‐side voltage controller of the LCC‐HVDC station can highly impact the damping of the oscillatory modes and even cause instability. The studies also show that the voltage control parameters can be selected to prevent PLL‐induced instability. The studies also (i) show that maximum available power and critical SCR are highly affected by PLL and DC‐side voltage control and (ii) propose a procedure to systematically determine these indices.
No takes yet. Share an insight, caveat, or question.
Guo et al. (2017) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: