High-frequency transformer models for use in system transient studies should include the transformer’s frequency-dependent effects to give reliable simulation results. The most accurate white-box modeling approach is based on the branch impedance matrix Z b with inclusion of frequency-dependent effects, in combination with the capacitance matrix. The required calculation of Z b at many time frequency samples using FEM can be very time consuming, due to the large dimension of Z b . We show that the frequency dependency in Z b can be approximately taken into account by an empirical frequency response that is derived from an eigenvalue of Z b from a representative transformer. That way, the long computation time by FEM is avoided. The proposed method is demonstrated to be more accurate than usage of the classical Fergestad’s damping factor method.
No takes yet. Share an insight, caveat, or question.
Gustavsen et al. (2026) studied this question.