PT Indofood CBP Sukses Makmur Tbk, Food Seasoning Division, requires a reliable electrical system to ensure production continuity. This study evaluates the operational feasibility and electrical safety compliance of generators, AC motors, distribution panels, and lightning protection systems through inspection and technical testing. The results show that the genset components are in good condition, but the noise reaches 105.2 dB near the machine and 97.2 dB at distance of 3 meters. The AC motor has an average insulation resistance of 21.8 MΩ, DAR 1.2–1.4, and PI 1.0–1.5, meaning it can still operate with regular monitoring. The phase-to-phase voltage of the PHB is 398–400 V, indicating a stable distribution system, while the lightning conductor grounding resistance of 0.21 Ω shows effective grounding. Overall, the electrical installation is suitable for operation, with recommendations to control genset noise and regularly monitor motor insulation conditions.