Answers are grounded in this paper and cite their sources.
Mixed-mode offices in sub-Saharan hot semi-arid climates face growing thermal stress, yet long-term evidence remains scarce. This study addresses this gap via a stress-test framework (RCP8.5) applied to a compressed earth bricks office in Ouagadougou, Burkina Faso. A calibrated DesignBuilder/EnergyPlus model evaluated four strategies—free-running (FR), natural ventilation (NV), mixed-mode (MM), and fully air-conditioned (AC)—under current (2023) and future horizons (2030, 2060, 2090). Thermal comfort was assessed using ASHRAE-55 adaptive (80%) for FR, NV, and MM, and PMV-PPD for AC. Results show that outdoor temperatures rise by +0.73 °C (2030), +2.6 °C (2060), and +4.71 °C (2090). Passive-only strategies maintain zero energy but show severely growing discomfort. Under AC27, energy demand reaches 282.6 kWh/m2·year by 2090. MM27 reduces discomfort from 9.8% (2023) to 28.1% (2090) while consuming about half the energy of full AC (124.7 kWh/m2·year by 2090), corresponding to an AC/MM energy ratio of 1.9 to 2.3 times. The share of occupied hours with windows open falls below 50% already in 2023, and below 30% between 2030 and 2060—a transition toward cooling-dominated behaviour not previously quantified for the Sudano-Sahelian zone. These findings support mixed-mode as a climate-contingent strategy for sub-Saharan offices, though validation across multiple zones and typologies is needed.
No takes yet. Share an insight, caveat, or question.
Bouda et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: