Key points are not available for this paper at this time.
This paper describes a simple, very reliable and extremely fast load-flow solution method with a wide range of practical application. It is attractive for accurate or approximate off-and on-line routine and contingency calculations for networks of any size, and can be implemented efficiently on computers with restrictive core-store capacities. The method is a development on other recent work employing the MW-Θ/ MVAR-V decoupling principle, and its precise algorithmic form has been determined by extensive numerical studies. The paper gives details of the method's performance on a series of practical problems of up to 1080 buses. A solution to within 0.01 MW/MVAR maximum bus mismatches is normally obtained in 4 to 7 iterations, each iteration being equal in speed to 1½ Gauss-Seidel iterations or 1/5th of a Newton iteration. Correlations of general interest between the power-mismatch convergence criterion and actual solution accuracy are obtained.
Building similarity graph...
Analyzing shared references across papers
Loading...
B. Stott
University School
O. Alsaç
Nexant (United States)
IEEE Transactions on Power Apparatus and Systems
University of Manchester
Institute of Science and Technology
Building similarity graph...
Analyzing shared references across papers
Loading...
Stott et al. (Wed,) studied this question.
synapsesocial.com/papers/6a15b17398b62c6f539f6825 — DOI: https://doi.org/10.1109/tpas.1974.293985