To address the stringent insulation safety requirements of modern high-voltage transformers, accurately characterizing the transient electric field is critical. However, a significant problem remains: current engineering models typically rely on static capacitive distributions, failing to capture the dynamic electric field distortion induced by rapid space charge injection under lightning impulses. Therefore, a non-contact spatial electric field measurement method based on the optical Kerr effect was employed to analyze the influence of electrode material, voltage amplitude, and wavefront time. Unlike traditional simulation models that often assume constant mobility and focus solely on the shielding effect, this study reveals a non-monotonic electric field evolution driven by a ‘Static-Dynamic’ mode transition. The proposed model highlights two critical breakthroughs: (1) Mechanism Innovation: It experimentally verifies that charge injection is governed by the ion charge-to-mass ratio rather than just the work function, leading to a newly identified field enhancement phase during the wavefront that overcomes the limitations of capacitive models that underestimate transient stress. (2) Parameter Quantification: Precise spatiotemporal thresholds are established—negative charges traverse the gap within ~200 ns, while positive charges require ~10 μs to reach equilibrium. These findings provide experimentally calibrated time constants for simulation correction and offer new criteria for optimizing electrode materials in UHV transformers to mitigate transient field distortion.
Zhao et al. (Wed,) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: