Analysis reveals enhanced reactive power regulation in variable-speed pumped storage units, indicating potential for efficiency gains.
Based on the actual data of a 300 MW doubly-fed variable speed pumped storage units (DFVSPSUs) in China, the reactive power characteristics of both the stator side and the grid-side converter are analyzed, and the reactive power regulation capability of the unit is discussed. First, the power coupling relationship is analyzed, demonstrating that the reactive power-regulation capability is jointly composed of the stator side and the grid-side converter, without direct coupling between them. Next, we determine the doubly-fed induction generator (DFIG) capacity, explaining that the capacity of the DFIG exceeds the rated capacity of the unit. Then, we note that the stator-side reactive power regulation capability is limited by prime mover power, stator current, and rotor current, while the grid-side converter regulation capability is influenced by converter capacity and rotor-side real power. Furthermore, the stator-side, grid-side converter and total reactive power-regulation capabilities of the unit under different water heads and real power conditions are determined. The results demonstrate that fully considering the grid-side converter can increase the unit’s reactive power regulation capability by 12% to 26%. Finally, by comparing the reactive power operating ranges of fixed-speed and variable-speed units, the reactive power advantages of the variable-speed unit are quantified.