Simulation reveals absorption chillers achieve up to 56% exergy efficiency under different climatic conditions, suggesting optimization opportunities.
This work mainly focuses on the energy and exergy analysis of a single-effect absorption cooling system operating with the couple H2O-LiBr, under different climatic conditions in Senegal and France. A simulation model was developed, using the Engineering Equation Solver V10 (EES) software. Results indicate that the system can achieve a maximum COP of 0.76 and an exergy efficiency of 56%, which decreases as the generator temperature increases. Increasing the generator temperature from 87 to 95 °C significantly improves COP, but gains become marginal beyond 100 °C. The highest exergy destruction occurs in the generator, followed by the absorber, condenser, and evaporator. A temperature difference above 44 °C between the generator and the absorber is required to maintain H2O-LiBr solution stability. Optimal temperatures for hot climates like Senegal are 90 °C (generator), 42 °C (absorber/condenser), and 7 °C (evaporator), while maximum exergy efficiency (56%) is reached at 81 °C, typical of moderate climates (France). Evaporator exergy efficiency increases from 16 to 52% with rising ambient temperature, while absorber and condenser efficiencies drop. Increasing the cooling water flow rate from 0.2 to 1.4 kg/s reduces exergy losses in the absorber and the condenser by up to 36%. The solution heat exchanger (SHE) optimal effectiveness of 0.75 reduces exergy consumption in the absorber and the generator.
No takes yet. Share an insight, caveat, or question.
Sow et al. (2025) studied this question.
Synapse has enriched 2 closely related papers on similar clinical questions. Consider them for comparative context: