This analysis evaluates four control strategies for chilled water systems, suggesting enhancements in energy consumption and operational efficiency.
Water distribution and pumping systems consume a large share of energy in metro HVAC operations and remain a major challenge to energy-efficient performance. This study, grounded in a practical metro project, investigates four control strategies for chilled water systems, focusing on chiller sequencing, pump frequency modulation, and variable flow regulation. A dynamic system model was developed using Dymola to simulate and evaluate the performance of each strategy. The results indicate that Strategy 2, which integrates real-time outdoor weather parameters into the frequency control logic, enhances operational stability and maintainability while achieving a 4.42% reduction in total energy consumption compared to the baseline. Strategy 4 employs a genetic algorithm to optimize chiller load distribution, resulting in improved system efficiency and energy savings of up to 8.62%. Further analysis reveals that chillers account for approximately 80% of the system’s total energy consumption, underscoring their central importance in system-wide energy optimization. Additionally, cooling towers show significant energy-saving potential under low wet-bulb temperatures. A 1 °C decrease in wet-bulb temperature results in an estimated 7% reduction in energy use. These findings offer quantitative insights and practical guidance for the low-carbon optimization of metro chilled water systems.
No takes yet. Share an insight, caveat, or question.
Zhu et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: