Experimental study shows the impact of hot gas and residual arc on current interruption failures, indicating novel insights into reignition phenomena.
This study experimentally investigated the influences of a hot gas and residual arc on current interruption failure in a modeled air switchgear installing splitter plates, using a four-wavelength spectroscopic imaging sensor for the judgement of thermal or dielectric reignition. Experimental results showed that the interruption failure was observed both inside and outside the arc-extinguishing box. The hot gas outside the box caused thermal reignition due to retention effects caused by combustion reactions, while the residual arcs inside the box caused not only thermal reignition but also dielectric reignition. These experimental results demonstrated that spatiotemporal dynamics of hot gas and residual arcs significantly influences the reignition phenomena in the air switchgears, which can not be directly explained by traditional reignition mechanisms.
No takes yet. Share an insight, caveat, or question.
Hiraide et al. (2025) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: