Analysis shows the effect of primary air ratio on thermal efficiency in a circulating fluidized bed boiler, suggesting optimal settings may improve performance.
In order to solve the problem of low thermal efficiency of a 130 t/h industrial circulating fluidized bed boiler, a computational particle fluid dynamic approach was used in this work to study two-phase gas–solid flow, heat transfer, and combustion. The factors influencing coal particle size distributions, air distribution strategies, and operational loads are addressed. The results showed that particle distribution exhibits “core–annulus” flow with a dense-phase bottom region and dilute-phase upper zone. A higher primary air ratio (0.8–1.5) enhances axial gas velocity and bed temperature but reduces secondary air zone (2.5–5.8 m) temperature. A higher primary air ratio also decreases outlet O2 mole fraction and increases fly ash carbon content, with optimal thermal efficiency at a ratio of 1.0. In addition, as the coal PSD decreases and the load increases, the overall temperature of the furnace increases and the outlet O2 mole fraction decreases.