The proposed algorithm optimizes damping ratios in power systems, highlighting improvements in stability and robustness.
Low-frequency oscillation modes are studied in small-signal angular stability because, if not adequately damped, they can cause power system instability in the event of a contingency. The interconnection and expansion of large power systems has led to the emergence of multiple local and inter-area modes and required new damping control strategies for these modes. The expansion of the use of Phasor Measurement Units in power systems has led to the development of new control strategies such as Wide-Area Damping Controllers (WADCs) that use data from PMUs to dampen low-frequency oscillations. Although the benefits of WADCs are promising, there are challenges in designing a WADC. This paper proposes a two-stage algorithm for the robust design of a WADC for modern power systems. The first stage consists of solving an optimization model and finding the WADC parameters that maximize the damping ratios of all modes of the linearized system model for a set of operating points. The second stage consists of refining the WADC parameters through an iterative algorithm. Cases were studied for a set of IEEE 68-bus operating points through modal analysis and time-domain simulations. The results obtained demonstrated the good performance of the proposed two-stage algorithm compared with an existing WADC design method based on a Linear Quadratic Regulator.