Answers are grounded in this paper and cite their sources.
In this article, we address the problem of delay-causing time synchronization (DC-TS) attacks against wide-area damping controllers (WADCs). To enhance smart grid stability against such threats, we present a realistic and secure design procedure for WADCs. To this end, we follow a methodology that utilizes the state-space model of the entire grid to design a periodic observer-based event-triggered controller by formulating the problem as a set of linear matrix inequalities, solved by the looped-Lyapunov functional (LLF) technique. The event-triggered scheme applied in this design procedure improves communication efficiency. Plus, the periodic sampled-data approach makes the design better suited to the operational reality of digital systems and their constraints. As such, the contributions of this work include developing an event-triggered mechanism to reduce unnecessary data transmissions, applying LLF for less conservative stability analysis, and utilizing the Guardian map theorem and Rekasius substitution to assess the WADCs resilience under DC-TS attacks. We conducted extensive simulations on the Kundur two-area and New England 39-bus systems to validate our approach. These simulations, along with comparisons to existing methods and tests on the RT-Lab real-time platform, demonstrate the superior performance of our WADC in maintaining grid stability and improving damping under considered attacks.
No takes yet. Share an insight, caveat, or question.
Vahidi et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: