This paper investigates the impacts of small-scale distributed energy resources (DERs) on fault currents and overcurrent protection (OCP) coordination in distribution feeders, considering the Brazilian regulatory framework. Changes in fault current levels and OCP coordination are analyzed by focusing on the relationships between DER location, output power, and OCP positioning. Simulations were conducted in Simulink/MATLAB using the IEEE 13-Node Distribution Test Feeder as a case study, considering various DER integration scenarios. The DER model adheres to the Brazilian standard NBR 16149:2013, which governs fault current injection and voltage ride-through behavior. The results indicate that DER integration can disrupt OCP coordination and significantly affect fault current levels, despite their relatively small current contributions during faults. In one scenario, OCP coordination was lost, while in others, coordination time intervals decreased. The findings show that DER location has a minimal influence on fault current changes, whereas output power plays a more critical role. Faults occurring farther from the substation cause greater current variation in installed relays, with deviations nearing ±10%. Additionally, reverse fault currents through relays are identified as a key concern for protection engineers.