This research demonstrates improved arc-extinguishing techniques in 10 kV lines, highlighting the effectiveness of trifluoroiodomethane gas.
Plasma arcs generated by lightning strikes are prone to tripping distribution lines, especially 10 kV lines. To reduce the lightning-induced tripping rate of 10 kV distribution lines and ensure the safe operation of power systems, this paper proposes a same-level double-fracture lightning protection device containing the electronegative gas trifluoroiodomethane (CF3I). A mathematical model of the gas arc-extinguishing process is established based on magnetohydrodynamics. Meanwhile, the mechanism of CF3I in the arc-extinguishing process is analyzed according to its physical and chemical properties, and the arc-extinguishing process is simulated using COMSOL Multiphysics 6.0. The results show that (1) the arc-extinguishing effect is optimal when the horizontal distance of the compression pipeline of the device is 9 mm; (2) under the action of power frequency currents with different initial phases of π/2 and 0, the arc-extinguishing device can extinguish the arc within 800 without re-ignition; and (3) in the arc-extinguishing process involving CF3I, the arc can be extinguished within 710 , which is 11.2% quicker than that without CF3I. Meanwhile, CF3I can effectively reduce the arc temperature at the initial stage of arc extinguishing, avoiding damage caused by excessive internal compression of the device.