This analysis examines the effect of water mist on flame extinction in methane-air mixtures, suggesting critical parameters for fire suppression systems.
In this study, a McKenna burner made for calibration is used to generate the laminar flame with the equivalence ratio of 0.78~2.0. The effect of the downward water mist spray on the extinction of the methane–air premixed laminar flame is investigated using hydroxide planar laser-induced fluorescence (OH-PLIF). The variation of the water flow rate for flame extinction is analyzed by the hydroxyl radical concentration distribution and the effective water mist flow rate. The required water flow rate for flame extinction is higher in the cases of rich fuel mixtures. The maximum critical extinguishing water flow rate for the methane–air premixed laminar flame is about 9.55 L/min under the conditions of water mist spray with a 45° solid cone spray angle and a 24 μm droplet size. Furthermore, the evolution of OH-PLIF flame behavior revealed that the stability of the hydroxyl radical concentration at the base of the flame mainly contributed to the flame extinction. This study provides a theoretical reference for the critical extinguishing conditions of water mist in the application of an active fire suppression system.