Answers are grounded in this paper and cite their sources.
Exergy analysis reveals 17.3% efficiency in an absorption cooling system, suggesting improvements with alternative steam sources.
An artificial intelligence (AI)-based exergy analysis of an absorption cooling system (ACS), utilizing a lithium bromide–water refrigeration cycle, is presented in this paper. The ACS is characterised by the utilisation of the intermediatepressure (IP) extraction steam from the steam turbine for its operation. The exergy analysis of the ACS is detailed, based on AI modelling through a machine learning algorithm, which predicts and optimises the ACS performance. The machine learning algorithm is validated using real process data obtained through ACS measurements via the supervisory control and data acquisition (SCADA) system. The AI results show that the ACS generates 126.71 kW of cooling for district cooling and 279.57 kW of heat, which is used for heating demineralised water. During the analysis period, the ACS consumed an average of 152.86 kW of IP steam, and operated with an average exergy efficiency of 17.3%. The study suggests that the average exergy efficiency of the ACS could be improved by using lower-quality steam, or even hot water, for operation.
No takes yet. Share an insight, caveat, or question.
Dušan Strušnik (2025) studied this question.
Synapse has enriched 8 closely related papers on similar clinical questions. Consider them for comparative context: