Aiming at the problems of low equipment utilization and the high-capacity requirements of existing arc-suppression devices, a multi-functional reactive power compensation device with the capability of grounding fault regulation (MF-RPCD) is proposed. Firstly, the topology and operation mechanism of MF-RPCD are introduced in this paper. MF-RPCD works in a reactive power compensation mode when a power grid is under normal operation to ensure the unit power factor operation of the power-grid side. When a single line-to-ground fault occurs in the power grid, MF-RPCD works in a fault-regulation mode to effectively suppress the ground-fault current. Secondly, the parameters of the active and passive parts of MF-RPCD are optimally designed to ensure the stable operation of MF-RPCD. Finally, the correctness, feasibility and effectiveness of the proposed topology and functions are verified using simulations and experiments.