Comparative assessment demonstrates improved temperature stability in deep borehole heat exchangers, indicating plate coupled heat pumps provide optimal performance.
With the transition towards renewable energy sources, particularly as we move away from fossil fuels, there has been a constant evolution of deep borehole heat exchanger (DBHE) coupled heat pump heating technology. On the basis of the heat-exchanging properties of circulating fluid in the DBHE heating system, this paper clarifies the setup forms of this system, and elucidates the influence of heat extraction performance. After analysis and research, it can be concluded that the direct supply mode shows a more prominent decline in water temperature compared to the coupled heat pump and coupled plate heat exchanger modes. The imported and exported water temperatures when heating ends were recorded as 9.98°C and 16°C, respectively. The imported and exported water temperatures for both the direct supply and the coupled plate heat exchanger modes tend to be similar at 19.6°C and 25.5°C at a temperature of 7°C. Heat pump not only enhances the heat exchange features of ground source heat pump (GSHP) heating system, but also defines the configuration of heat extraction performance of DBHE. The system power consumption in the coupled plate heat exchanger mode is lower than that in the heat pump mode which is conducive to stable operation. Therefore, the best design form of the DBHE Heating System is the heat pump coupled plate exchange mode.
No takes yet. Share an insight, caveat, or question.
Zhu et al. (2024) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: