The article is devoted to the features of physical modeling of single-phase earth faults in 6-35 kV networks in laboratory conditions. Such damage is not associated with the occurrence of short circuit currents. The ground fault currents flowing at the fault site are tens of times less than the load currents. Therefore, traditional current protection, such as current cut-off or overcurrent protection, is unsuitable for detecting such faults. The insulation condition is monitored using voltage transformers, in which one of the secondary windings is connected in an open delta. When a ground fault occurs, the resulting asymmetrical mode causes the appearance of a zero-sequence voltage 3·U ̇_0, the magnitude of which depends on the resistance at the location of the fault. A voltage relay connected to this winding completes the signal circuits. The low-voltage windings of power transformers are connected in a triangle, so the line voltages during single-phase ground faults remain unchanged, and the consumer can receive power. Network operation in asymmetrical mode is limited to two hours due to overloading of the insulation of healthy phases, the possible occurrence of an intermittent arc and overheating of electric motor rotors.