Ground heat exchanger (GHE) is the most crucial element of a ground source heat pump (GSHP) system for building cooling and heating by the utilization of geothermal energy. Therefore, intending to enhance the performance of GHE, the present study conducts a computational investigation of the thermal performance of modified spiral tube vertical GHEs. Several modifications of uniform-pitched spiral GHE are made to increase its thermal performance. Some modifications are introduced as variable-pitched spiral tube GHE where spiral inlet pipes are densified in the lower part of GHEs by reducing pitch distance. Conversely, in some modifications, the position of the outlet straight pipe is changed. Water is considered as the working fluid and the inlet temperature of the water is maintained fixed at 300.15 K. After extensive analysis, it is evident that, when the outlet pipe is placed outside of the spiral coil, there is a 7.67 % enhancement in the thermal performance than a traditional uniform-pitched spiral tube GHE. However, modifications like variable-pitched spiral tube GHEs are not significant to improve the thermal performance due to the quick saturation of the ground soil temperature around the GHE pipes. To have a balance between heat transfer rate and pressure drop, thermal performance capability (TPC) and coefficient of performance improvement