The concepts of impedance matching and infinite feeder simulation are currently the mainstream solutions to the problem of background harmonic propagation and magnification on distribution feeders, and their principle is to eliminate reflected waves, which can dampen the harmonic voltage-magnifying factor to around 1. The standing wave compensation mitigation scheme proposed in this letter is based on a completely different concept, which can extend the feeder length to an integer multiple of the harmonic wavelength equivalently by constructing a virtual feeder. At this time, the reflection effect does not disappear but transfers to another state, and the maximum harmonic voltage-magnifying factor on the feeder is limited to 1. Furthermore, since the magnifying factor at most positions on the feeder is obviously lower than this limit, the proposed standing wave compensation-based active power filter (SWC-APF) can obtain significantly better mitigation performance than conventional schemes regardless of the installation location, and the required power capacity will not increase. Finally, the experimental results verify the effectiveness of the proposed scheme.