Answers are grounded in this paper and cite their sources.
Quenching of excess aqueous ozone (O3) residual is needed to avoid off-gassing and oxidative damage to downstream components. Eight quenching agents (QAs), calcium thiosulfate (Ca-Thio), sodium bisulfite (Na-Bi), hydrogen peroxide (H2O2), sodium thiosulfate (Na-Thio), sodium metabisulfite (Na-Metabi), potassium metabisulfite (K-Metabi), sodium sulfite (Na-S), and ascorbic acid (AscAcid) were tested at varying pHs (7.5, 7.9, and 8.5) and temperatures (4°C, 15°C, and 23°C). Temperature had significant effects on initial quenching (≤30 s), with less occurring at 4°C than 23°C; but with extended contact time this trend reversed. Quenching efficiency was not substantially affected by pH. Ca-Thio and Na-Thio were inefficient but quick, had lower mass requirements, and minimal handling concerns. Na-Metabi, Na-Bi, and Na-S were quick and efficient, but K-Metabi was the only QA that quenched (26–31%) less O3 than stoichiometry at all conditions. These sulfite-based QAs had more handling concerns and greater mass requirements. H2O2 was slower than other QAs but 2–9× quicker than predicted by rate coefficients and efficient when given longer contact time (≤5 min). H2O2 had some handling concerns but the lowest mass requirements (assuming 5 min contact time) and creates desirable AOP conditions. AscAcid consistently quenched (22–113%) more O3 than the stoichiometric ratio but had higher mass requirements, except in colder temperatures. Hydrodynamics, QA-diffuser design, and supply chain were also important considerations.
No takes yet. Share an insight, caveat, or question.
Atkinson et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: